Veevaba WG2A nutikas loogikakontroller

Tooteteave
Tehnilised andmed
- Mudel: nutikas loogikakontroller
- Funktsioonid: PLC funktsioonid ja järjestused
- Tootja: Total Green Mfg.
- Juhtimine: PLC-ga juhitav
- Stage: 2-stage- ja multifunktsionaalsed seadmed
- Ühilduvus: Töötab erinevate kütte-/jahutustermostaatidega
Vastutusest loobumine
Total Green Mfg. soojuspumba nõuetekohane paigaldamine ja hooldamine on selle usaldusväärse töö tagamiseks hädavajalik. Kõik Total Green Mfg. süsteemid peab paigaldama ja hooldama kvalifitseeritud HVAC-töövõtja. Seadmete suuruse määramine, valik ja paigaldamine on ainuüksi paigaldaja vastutusel.
Installations of equipment on an existing copper earth loop design that does not match a current Total Green Mfg. earth loop design is not permitted, will void all warranties on the equipment, and are the sole responsibility of the installing contractor. Installation must be made in accordance with the instructions set forth in this manual. Failure to provide installation by a qualified HVAC contractor in a manner consistent with this manual will void and nullify the limited warranty coverage for the system.
Total Green Mfg. ei vastuta otseste või kaudsete defektide, mitterahuldava jõudluse, kahjustuste või kadude eest, mis on seotud mis tahes kohapeal määratletud komponentide projekteerimise, tootmise, ehitamise, kasutamise või paigaldamisega.
Kõik Total Green Mfg. 2 stagMadala mahutavusega e- ja multifunktsionaalsetel seadmetel on eraldi klemmliistud sildiga „termostaat/tsooniplaat“ ja „õhukäitleja/ahi“.tage ja on PLC-ga „juhitavad”.
Seadme nõuetekohaseks toimimiseks peab termostaat või tsooniplaat olema ühendatud termostaadi/tsooniplaadi klemmliistuga. Õhukäitlusseade või ahi peab olema ühendatud õhukäitlusseadme/ahju klemmliistuga. Lisaks on olemas täiendavad klemmliistud erinevate funktsioonide jaoks, olenevalt teie kasutatavast mudelist. Siin esitatud teave on mõeldud teie seadme paigaldusjuhendi täiendamiseks.
TÄHTIS: For WG2A, WG1AH, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.
Nutikas loogikakontroller
WG2A Forced Air Only– List of functions
- The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to
“X”. During this 60 second time period, the compressor will only operate in 1st stage andes süsteemile vaid võimaluse taastuda enne jäiga lukustuse seadistamist. See on vajalik ebameeldivate kõnede vältimiseks, eriti jahutusperioodi alguses, kui maanduskontuurid on kõige külmemad. „X“ määratakse mis tahes jäiga lukustuse tingimuse korral. Madala helitugevuse sisselülitaminetagKompressoriseadme väljalülitamine ja uuesti sisselülitamine lähtestab lukustuse, kui tühjendustemperatuuri lüliti pole avatud. Väljalasketemperatuuri lülitil on käsitsi lähtestamise nupp. Avatud tühjendustemperatuuri lüliti vajab alati käsitsi lähtestamist koos madala mahutavusega.tage toitetsükkel. Rõhulülitid on automaatsed. - A “Y1” call starts 1st stage küte või jahutus, mis kestab 20 minutit ja seejärel aeg teise sekundinitagKui see aeg möödub ilma, et termostaat helistaks numbrile „Y2“. Kui seade on kütterežiimis, siis pärast teist sekundittagKui küttesüsteem käivitub ja küttevajadus pole täidetud, lülitab 20-minutiline taimer sisse lisakütte. Kui kõik on tehtud, lülitab see sisse XNUMX-minutilise taimeri.tagKui funktsioone on kutsutud, jäävad need kutsutuks, kuni termostaat rahuldab täielikult ootused.
- If more than 3 consecutive “Y1” calls take place without the thermostat calling for 2nd stage 20 minuti jooksul või enne 20-minutilist teist sekundittagKui taimer saab täis, neljanda „Y1” kõne ajal käivitub hooldustsükkel, mis hoiab süsteemi ootel ja lukustab selle 2. sekundisse.tage 5 minutiks, et tagada õli tagasivool kompressorisse. Kui süsteem on õhutsooniks jaotatud, aktiveerub tsooni tühistamise klemm „D” 24 voldini. Nagu seadme paigaldusjuhendis kirjeldatud, saab seda 24-voldist signaali kasutada koos kohapeal tarnitava isolatsioonireleega, et avada suurim tsoon ja hoida seda d.ampavada, et puhur ei kogeks nende 5 minuti jooksul kõrget staatilist rõhku. Hooldustsükkel lukustab kõik muud kõned kuni nende lõpuni. Pärast hooldustsüklit või kui enne hooldustsükli algust tehakse kõne „Y2“, lähtestatakse loendur uuesti nulli. See muudab meie süsteemi tsoonisõbralikuks, kuna see võimaldab tõelist 2 sekundit.tagküte ja jahutus.
- There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
- When the thermostat is set to cooling mode, the “O” signal energizes the reversing valve and locks out the aux heat output.
- In an effort the reduce energy consumption, the PLC turns power off to the crank case heater when the compressor runs.
- This PLC program also allows the use of almost any heat/cool thermostat. Even if a single stagKui kasutatakse ainult kütte-/jahutustermostaati, juhib PLC-programm kõiki funktsioonetag2. stage ja AUX Heat vastavalt vajadusele.
WGxAH Üksik ja kaks Stage Sundõhk hüdroküttefunktsiooniga
In addition to the function and features as described for WG2A units, The PLC program for the WGxAH units allows for switching priority call from forced air to hydronic heating as well as a feature
called “Split Zone” that are installer optioned by choosing jumper settings as described below.
- A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating over hydronic heating. When this jumper is removed, hydronic heating becomes the priority call.
- Split Zone is a feature which allows you the ability to heat one zone or floor with hydronic heat and another zone or floor with forced air. Split Zone is active by removing the priority call jumper across “R” and “AW” moving it across the “R” and “SZ” of the field wiring terminal block.
- While in “Split Zone” mode, the compressor unit will provided forced air heating to the air zone. When the buffer storage tank calls for heat, the compressor unit will shift to heat water. Should a call for the air zone take place while the compressor unit is heating water, the call goes directly to the aux heat source to maintain the air zone. Once the tank temperature is satisfied, the system diverts back to normal air heating with the compressor unit.
- When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
- The Hydronic heating function is disabled anytime the “O’ terminal is energized placing the unit in cooling mode.
WG2AD sundõhuga ja tarbevee soojendamise funktsiooniga
Lisaks selle dokumendi esimeses osas WG2A seadmete jaoks kirjeldatud funktsioonidele ja omadustele võimaldab WG2AD seadmete PLC programm lülitada prioriteetkõne sundõhult tarbevee soojendamisele.
- A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating/cooling over domestic water heating. When this jumper is removed, domestic water heating becomes the priority call.
- When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
- An added functional PLC feature exclusive to the WG2AD model which allows water heating up 120 degrees, is the unit’s ability to maintain compressor stability by throttling the compressor load as needed to control discharge pressure.
WG1H 100% Hydronic Heated and Chilled Water Only– List of functions
- The PLC checks that the LOW/HIGH pressure, HX Low and Discharge temperature switches are made. An open safety switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagKompressoriseadme väljalülitamine ja uuesti sisselülitamine lähtestab lukustuse, kui tühjendustemperatuuri lüliti pole avatud. Väljalasketemperatuuri lülitil on käsitsi lähtestamise nupp. Avatud tühjendustemperatuuri lüliti vajab alati käsitsi lähtestamist koos madala mahutavusega.tage toitetsükkel. Rõhu- ja HX madala temperatuuri lülitid on automaatsed.
- An “N” call starts the circulator pump for 30 seconds prior to the compressor to allow for full flow through the HX (heat exchanger) prior to starting the compressor. Once the call is complete, the pump will run an addition 30 seconds after the compressor stops to purge the HX of any residual heat. This occurs regardless of either a heated or chilled water call.
If you have any questions regarding any of these functions, please contact Total Green Mfg. at 419-678-2032 tehnilise toe saamiseks.
Korduma kippuvad küsimused
- K: Kuidas seada WGxAH seadmetes õhukütet hüdroküttele esikohale?
A: Remove the jumper between R and AW terminals on the field wiring terminal strip. - K: Kuidas töötab jagatud tsooni funktsioon WGxAH seadmetes?
A: Move the jumper from R and AW terminals to R and SZ on the field wiring terminal block to activate Split Zone.
Dokumendid / Ressursid
![]() |
Veevaba WG2A nutikas loogikakontroller [pdfKasutusjuhend WG2A, WG1AH, WG2AH, WG2AD, WG2A nutikas loogikakontroller, WG2A, nutikas loogikakontroller, loogikakontroller, kontroller |