1. Sissejuhatus

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Acrel DTSD1352 Three Phase Bidirectional Energy Meter. This device is designed for accurate measurement of three-phase energy consumption and generation, featuring RS485 communication for integration into monitoring systems. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.

2. Ohutusalane teave

HOIATUS: Elektrilöögi oht!

  • Paigaldamist ja hooldust tohivad teha ainult kvalifitseeritud elektrikud.
  • Ensure all power is disconnected before installing or servicing the meter.
  • Ärge puudutage pingestatud klemme.
  • Verify correct wiring connections to prevent damage to the meter or electrical system.
  • The meter must be installed in a dry, well-ventilated area, free from excessive dust, corrosive gases, and direct sunlight.

3. Toote lõppview

The Acrel DTSD1352 is a compact and robust three-phase multi-function energy meter. It features a clear LCD display for real-time data, intuitive control buttons, and various connection terminals.

Esiosa view of the Acrel DTSD1352 energy meter showing the LCD display, control buttons, and terminal connections.

Joonis 3.1: Esiosa view of the DTSD1352 meter. This image displays the main LCD screen showing power readings (e.g., 0.00 kW), the "SET" button, and three orange arrow buttons for navigation. Terminal blocks are visible at the top and bottom for electrical connections.

Nurga all view of the Acrel DTSD1352 energy meter, showing the side profile and additional terminal details.

Joonis 3.2: Nurga all view of the DTSD1352 meter. This perspective highlights the compact design and the various input/output terminals on the top and bottom, as well as the side labeling for model identification.

4. Tehnilised andmed

The following table outlines the key technical specifications of the Acrel DTSD1352 energy meter. For detailed information, refer to the product datasheet.

Table of technical specifications for the Acrel DTSD1352 energy meter, including voltage, current, measurement performance, pulse, communication, outline, and environment details.

Joonis 4.1: Detailed technical specifications. This image presents a table covering various parameters such as reference voltage (3*57.7/100V, 3*220/380V, 3*380V), reference frequency (50Hz), maximum current (6A, 80A), accuracy (Class 0.5S), communication interface (RS485, MODBUS-RTU), dimensions (127*88*70 mm), and environmental conditions (operating temperature -25~55℃, humidity ≤95%).

Tabel 4.1: Üldised spetsifikatsioonid
ParameeterVäärtus
Viide Voltage3*57.7/100V, 3*220/380V, 3*380V
Võrdlussagedus50 Hz
Maksimaalne vool6A, 80A (depending on model)
Accuracy of active kWhKlass 0.5S
SideliidesRS485
SideprotokollMODBUS-RTU
Mõõdud (P*L*K)127mm * 88mm * 70mm
Töötemperatuur-25 ℃ kuni 55 ℃
Säilitustemperatuur-40 ℃ kuni 70 ℃
Niiskus≤95% (ilma kondensatsioonita)
Kõrgus merepinnast<2000m
Kauba kaal7.1 untsi (umbes 200 g)

5. Paigaldamine ja juhtmestik

Proper installation and wiring are critical for the accurate and safe operation of the DTSD1352 meter. Refer to the diagrams below for connection methods.

Wiring diagrams for the Acrel DTSD1352 energy meter, showing both direct connection (3P4W) and connection via Current Transformers (CTs).

Joonis 5.1: Wiring diagrams. This image illustrates two primary wiring methods: a 3-phase 4-wire (3P4W) direct connection where power lines (A, B, C, N) connect directly to the meter, and a connection via Current Transformers (CTs) for higher current applications, showing the CTs connected to the respective phase lines and then to the meter.

5.1 Direct Connection (3P4W)

For direct connection, ensure the phase lines (A, B, C) and neutral (N) are connected to the corresponding terminals on the meter. This method is typically used for lower current applications where the meter can directly handle the load current.

  • Connect Phase A to terminal 'A'.
  • Connect Phase B to terminal 'B'.
  • Connect Phase C to terminal 'C'.
  • Connect Neutral to terminal 'N'.
  • Veenduge, et kõik ühendused on kindlad ja korralikult isoleeritud.

5.2 Connection via Current Transformers (CTs)

For higher current applications, the DTSD1352 meter can be connected via external Current Transformers (CTs). This method scales down the current to a measurable level for the meter.

  • Install the CTs on each phase line (A, B, C).
  • Connect the secondary windings of the CTs to the corresponding current input terminals (e.g., Ia*, Ia, Ib*, Ib, Ic*, Ic) on the meter.
  • Ensure the polarity of the CTs is correct (P1/K to the source side, P2/L to the load side, and S1/S2 to the meter). Incorrect polarity will result in inaccurate readings.
  • Ühendage voltage inputs (Ua, Ub, Uc, N) directly from the respective phases and neutral to the meter.
  • It is recommended to install a fuse on the voltage input lines for protection.

Important: Always ensure the CT secondary circuit is closed before applying power to the primary circuit. Never open the secondary circuit of a live CT.

6. Operatsioon

Once installed and powered, the DTSD1352 meter will automatically begin measuring. The LCD display shows various parameters, which can be navigated using the control buttons.

6.1 Ekraani navigeerimine

  • LCD ekraan: Shows real-time measurements such as voltage, current, active power, reactive power, power factor, frequency, and total energy (kWh).
  • "SET" Button: Used to enter the parameter setting mode or confirm selections.
  • Arrow Buttons (Left, Right, Up, Down): Used to navigate through different display screens or adjust parameter values in setting mode.

6.2 Reading Energy Data

Press the arrow buttons to cycle through the various measurement screens. Common readings include:

  • Total Active Energy (kWh)
  • Forward Active Energy (kWh)
  • Reverse Active Energy (kWh)
  • Voltage (V) per phase
  • Current (A) per phase
  • Active Power (kW) per phase and total
  • Reactive Power (kVar) per phase and total
  • Võimsustegur (PF)
  • Sagedus (Hz)

6.3 RS485 side

The meter supports RS485 communication with MODBUS-RTU protocol. This allows for remote reading of meter data and configuration. Refer to the MODBUS communication protocol document for detailed register addresses and commands.

7. Hooldus

The DTSD1352 energy meter is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

  • Puhastamine: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Ühendused: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to inaccurate readings or overheating.
  • Keskkond: Veenduge, et töökeskkond jääks ettenähtud temperatuuri ja niiskuse vahemikku.
  • Kalibreerimine: The meter is factory calibrated. If you suspect inaccuracies, contact qualified service personnel for recalibration.

8. Veaotsing

This section provides solutions to common issues you might encounter with the DTSD1352 meter.

Tabel 8.1: Tõrkeotsingu juhend
ProbleemVõimalik põhjusLahendus
Mõõdiku näidik on tühi.Arvestil puudub toiteallikas.Check the main power supply and wiring connections to the meter's voltage input terminals. Ensure fuses are intact.
Inaccurate energy readings.Incorrect wiring, incorrect CT ratio setting (if applicable), faulty CTs, or meter malfunction.Verify all wiring connections according to Section 5. Ensure CT polarity is correct. Check if the CT ratio programmed in the meter matches the physical CTs. If issues persist, contact technical support.
RS485 side rike.Incorrect wiring of RS485 terminals (A/B), incorrect communication parameters (baud rate, parity, address), or software issue.Check RS485 A and B terminal connections. Verify communication settings (baud rate, data bits, stop bits, parity, meter address) in your master device match the meter's settings. Ensure proper termination resistors are used if necessary.
Meter shows "Error" or specific error codes.Sisemine rike või spetsiifiline tööprobleem.Note down the error code and consult the full product manual or contact technical support for specific error code interpretations and solutions.

9. Garantii ja tugi

This product is manufactured by TGLGTQPX and sold under the Acrel brand. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your vendor. General support for the Acrel DTSD1352 meter can be obtained through the manufacturer's official channels or your authorized distributor.

For technical assistance, troubleshooting beyond this manual, or spare parts, please contact:

  • Tootja: TGLGTQPX
  • Toote bränd: Acrel
  • Mudel: DTSD1352
  • (Contact information such as website or email would typically be provided here by the manufacturer.)

Seotud dokumendid - DTSD1352

Preview ADL100-ET ühefaasilise elektriarvesti paigaldus- ja kasutusjuhend
Põhjalik paigaldus- ja kasutusjuhend Acrel ADL100-ET ühefaasilise elektriarvesti jaoks. See juhend sisaldab tehnilisi kirjeldusi, funktsioonide kirjeldusi, juhtmestiku juhiseid, ekraanimenüüsid, programmeerimisprotseduure ja sideprotokolle (Modbus RTU).
Preview Acrel ADL3000 Smart Meter: Installation and Operation Manual
Comprehensive guide for the Acrel ADL3000 smart meter, covering installation, operation, technical specifications, and display functions for industrial and utility power monitoring.
Preview Acrel ADL400 Three Phase Electric Meter: Installation and Operation
Detailed information on the Acrel ADL400 three-phase electric meter, covering its general features, functions, electrical parameters, working environment, installation, and wiring diagrams for low-voltage energy measurement.
Preview Acrel D318 Harmonic Meter Operation Instruction Manual
Operation instruction manual for the Acrel D318 External Roche Coil and Switched Transformer Harmonic Meter. Details features, technical specifications, and connection methods for energy saving and power monitoring applications.
Preview Acrel ADL3000-E nutikas arvesti: paigaldus- ja kasutusjuhend
Acrel ADL3000-E nutika arvesti põhjalikud paigaldus- ja kasutusjuhised, mis hõlmavad tehnilisi kirjeldusi, juhtmestikku, ekraanifunktsioone ja sideprotokolle.
Preview DJSF1352-RN Rail-Mounted DC Power Meter Installation and Operation Manual
This document provides comprehensive installation and operation instructions for the Acrel DJSF1352-RN rail-mounted DC power meter. It covers product specifications, technical parameters, wiring diagrams, operational guidance, menu settings, and communication protocols (Modbus-RTU, DLT645-07).