This manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker. Please read this manual thoroughly before any operation.

The ABB SACE EMAX2 E2.2H 1600 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals and a solid-state release in AC EKIP/DIP-LI R 1600. It includes four auxiliary contacts and a circuit breaker in the open-closed position.

Peamised omadused:

  • Mounting type: Plug-In Mount
  • Voltage: 600.0 volts of alternating current
  • Circuit breaker type: Standard
  • Praegune hinnang: 1600.0 amps
  • Pooluste arv: 3
Esiosa view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker

Joonis 1: Esiosa view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing the Ekip Touch display, operating buttons (OPEN, Push OFF, Push ON), and the reset mechanism.

2. Seadistamine ja installimine

The ABB SACE EMAX2 E2.2 H 1600 is designed for plug-in mounting. Proper installation by qualified personnel is crucial for safety and optimal performance.

2.1 Lahtipakkimine ja ülevaatus

Carefully unpack the circuit breaker and all accessories. Inspect for any signs of shipping damage. Ensure all components listed in the packing slip are present.

ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker inside its wooden shipping crate

Figure 2: The circuit breaker securely packed within its wooden shipping crate, indicating careful handling during transport.

Accessories for the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, including mounting hardware and documentation, in clear plastic bags

Figure 3: Various accessories, such as mounting brackets and additional components, packaged separately for the circuit breaker.

2.2 Paigaldamine

This unit features a plug-in mount design. Refer to the detailed installation diagrams and instructions provided with the product for specific mounting procedures. Ensure the mounting surface is stable and capable of supporting the unit's weight (approximately 105.82 pounds).

2.3 Elektriühendused

Connect the main power lines to the designated terminals. The unit is a three-pole breaker. Ensure all connections are secure and comply with local electrical codes and standards.

Üles view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker showing the three main connection points with copper busbars

Joonis 4: Ülemine view illustrating the three main connection points for electrical wiring, designed for robust and secure connections.

Warning: All electrical work must be performed by a qualified electrician. Disconnect all power before installation or maintenance.

3. Kasutusjuhised

The ABB SACE EMAX2 E2.2 H 1600 features an Ekip Touch interface and mechanical push buttons for operation.

3.1 Põhitoimingud

  • To Close (Turn On): Press the "Push ON" button (green). The breaker will close, allowing current flow.
  • To Open (Turn Off): Press the "Push OFF" button (red). The breaker will open, interrupting current flow.
  • Avatud hädaolukorras: Use the "OPEN" lever for immediate manual opening.
  • Lähtesta: After a trip event, identify and resolve the cause. Then, press the "Reset" button to reset the tripping mechanism before attempting to close the breaker again.
Close-up of the operating panel of the ABB SACE EMAX2 E2.2 H 1600, showing the 'OPEN' lever, 'Push OFF' (red), 'Push ON' (green) buttons, and 'Reset' button.

Joonis 5: üksikasjalik view of the operational controls, including the Ekip Touch display and the mechanical buttons for opening, closing, and resetting the breaker.

3.2 Ekip Touch Interface

The Ekip Touch display provides real-time data, settings, and diagnostic information. Refer to the separate Ekip Touch user guide for detailed navigation and configuration instructions.

4. Hooldus

Regular maintenance ensures the longevity and reliable operation of your ABB SACE EMAX2 circuit breaker. Always disconnect power before performing any maintenance.

4.1 Rutiinsed kontrollid

  • Visually inspect the breaker for any signs of damage, loose connections, or excessive dust accumulation.
  • Veenduge, et ventilatsiooniavad oleksid vabad ja takistamata.
  • Check the integrity of all wiring and terminal connections.

4.2 Puhastamine

Use a dry, lint-free cloth to clean the exterior surfaces. Do not use abrasive cleaners or solvents. For internal cleaning, consult a qualified service technician.

Külg view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing internal mechanical components and gear assembly

Joonis 6: Külg view revealing the intricate mechanical components and gear assembly responsible for the breaker's operation, highlighting areas that may require professional inspection.

4.3 Professionaalne hooldus

Periodic professional servicing by ABB-certified technicians is recommended to ensure optimal performance and compliance with safety standards. This includes checking internal mechanisms and calibration of the Ekip Touch unit.

5. Veaotsing

This section provides general guidance for common issues. For complex problems, contact ABB technical support or a qualified electrician.

5.1 Breaker Trips Frequently

  • Ülekoormus: Check the connected load. Reduce the load if it exceeds the breaker's rated current (1600 A).
  • Lühis: Inspect wiring for short circuits. This requires immediate attention and professional diagnosis.
  • Maandusviga: If applicable, check for ground faults in the system.
  • Vigane varustus: Disconnect individual equipment to identify a faulty device causing the trip.

5.2 Breaker Does Not Close

  • Käivitatud olek: Ensure the breaker is fully reset after a trip. The "DISCHARGED SPRING" indicator might be visible if not reset.
  • Toide puudub: Verify incoming power supply.
  • Mechanical Obstruction: Check for any physical obstructions preventing the mechanism from closing.
Close-up of the product label on the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing model SACE E2.2H-A, serial number, ratings, and UL Listed certification.

Figure 7: Product label providing critical specifications such as model number (SACE E2.2H-A), serial number, rated maximum voltage, rated short-circuit current, and UL/CSA certifications.

6. Tehnilised andmed

Detailed technical specifications for the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker:

SpetsifikatsioonVäärtus
Product Main TypeSACE Emax 2
Mudeli numberSACE E2.2H-A
Nimivool (in)1600 A
Pooluste arv3
Praegune tüüpAC
Rated Voltage (Ur)690 V
Rated Operational Voltage690 V AC
Rated Insulation Voltage (kasutajaliides)Vahelduvvool 1000 V
Nimetatud impulsitaluvus voltage (Uimp)12 kV (acc. to IEC 60947-2)
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (525 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA, (230 V AC) 100 kA, (380 V AC) 100 kA, (400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (660 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Nimetatud lühiajaline vastupidavusvoolu madal voltage (Icw)for 1 s 85 kA, for 3 s 66 kA
Rated Uninterrupted Current (Iu)1600 A
Elektriline vastupidavusUe =<440 V 12000 cycle, Ue = 500 ... 690 V 10000 cycle (30 cycles per hour)
Mehaaniline vastupidavus25000 cycle (60 cycles per hour)
Võimsuse kaotus288 W
Toote mõõtmed15.08 x 12.48 x 16.73 tolli
Kaal105.82 naela
PäritoluriikItaalia

Note: Specifications are subject to change without notice. Always refer to the product label and official ABB documentation for the most accurate and up-to-date information.

Shipping label for ABB SACE EMAX2 E2.2 H 1600, showing product version, poles, overcurrent release type, and a barcode with the number 8057558336022.

Figure 8: Product identification label, including the EAN/UPC code 8057558336022, which can be used for product verification and lookup.

7. Garantii ja tugi

For warranty information and technical support, please refer to the official ABB documentation included with your product or visit the official ABB websaidile.

  • Tagastab: Sellel tootel on 30-päevane lihtne tagastusõigus. Lisateabe saamiseks vaadake jaemüüja tagastuspoliitikat.
  • Klienditugi: For assistance, contact customer support through your purchase platform or directly via ABB's official channels.
  • ABB Store: You can find more information and products from ABB by visiting the official ABB Store.

Seotud dokumendid - SACE E2.2H-A

Preview ABB SACE Emax 2: New Low VoltagÕhkkaitselülitite tehniline kataloog
Explore the ABB SACE Emax 2 series of new low voltage air circuit-breakers. This technical catalogue provides detailed information on features, ranges, protection trip units, communication, accessories, and specifications for efficient power management and system reliability.
Preview ABB SACE Emax 2 madal mahttagÕhkkaitselülitite tehniline kataloog
Põhjalik tehniline kataloog, mis kirjeldab ABB SACE Emax 2 seeria madalpingeseadmeid.tagõhk-kaitselülitid, mis hõlmavad täiustatud elektrijaotussüsteemide omadusi, spetsifikatsioone, kaitset, ühenduvust ja lisatarvikuid.
Preview ABB SACE Emax 3 External Electronic Accessories: Modbus, Profibus, Profinet, EtherNet/IP, IEC 61850, and More
Comprehensive guide to ABB SACE Emax 3 external electronic accessories, including Ekip Com modules (Modbus RTU, Profibus DP, Profinet, EtherNet/IP, IEC 61850), Ekip Signalling 2K, Ekip RELT, Ekip Synchrocheck, Ekip Temperature 4T, and Ekip Arc-Flash 6F. Details features, configuration, and installation.
Preview ABB SACE Tmax XT kataloog: Madal mahttagVormkorpusega kaitselülitid
Avastage ABB SACE Tmax XT seeriat, mis on tipptasemel madalpingeseadmete valik.tage molded case circuit-breakers offering advanced performance, connectivity, ease of use, and robust protection for diverse industrial and commercial applications.
Preview ABB SACE Emax 3 Circuit Breaker Accessories and Maintenance Guide
This document provides detailed information on the configuration, accessories, commissioning, and maintenance of ABB SACE Emax 3 circuit breakers, including Ekip Aware modules and related electronic accessories.
Preview ABB SACE Emax 2 Air Circuit-Breakers: Operating Instructions
Comprehensive operating instructions for ABB SACE Emax 2 low voltage air circuit-breakers, covering product selection, trip unit functions, accessories, and technical specifications for design engineers.