SENSOR SWITCH MP 20

MP20 Power Pack Instruction Manual

Mudel: MP 20 | Bränd: ANDURILÜLITI

1. Sissejuhatus

The SENSOR SWITCH MP20 Power Pack is a robust and reliable device designed to provide power and control for occupancy sensor systems. This power pack operates at 120/277VAC and can handle up to 20 amps, making it suitable for various commercial and industrial lighting control applications. It is engineered to be compatible with occupancy sensors, including those from different brands, offering flexibility in system integration. The MP20 is UL 2043 Plenum Rated, ensuring its suitability for use in air-handling spaces.

2. Ohutusalane teave

WARNING: Risk of electric shock. Installation should only be performed by a qualified electrician in accordance with all national and local electrical codes.

3. Seadistamine ja installimine

The MP20 Power Pack is designed for easy integration into existing or new lighting control systems. Follow these steps for proper installation:

  1. Toite katkestamine: Before beginning any wiring, ensure that power to the circuit is completely disconnected at the main breaker.
  2. Paigaldamine: Mount the MP20 Power Pack securely in a suitable junction box or electrical enclosure. Ensure adequate ventilation.
  3. Juhtmete ühendused: Refer to the wiring diagram below and the label on the device for precise connections. All connections must be made using appropriate wire nuts or connectors and insulated properly.
    • MUST traat: Connect to 120 VAC Line.
    • ORANGE Wire: Connect to 277 VAC Line (if using 277V system). If using 120V, cap and insulate this wire.
    • WHITE Wire: Ühenda neutraaliga.
    • BLUE Wires (2): These are Relay Contacts. Connect to the load (e.g., lighting fixtures).
    • RED Wire (Class 2): Connect to 15 VDC output from the occupancy sensor.
    • WHITE Wire (Class 2): Connect to Sensor input from the occupancy sensor.
    • BLACK Wire (Class 2): Connect to Common from the occupancy sensor.
  4. Turvalised ühendused: Double-check all wiring connections for tightness and proper insulation.
  5. Toite taastamine: Once all connections are secure and the device is properly mounted, restore power to the circuit.
SENSOR SWITCH MP20 Power Pack with wiring

Figure 1: SENSOR SWITCH MP20 Power Pack. This image displays the compact black rectangular device with various colored wires extending from its sides, including black, white, blue, orange, and red wires. The product label is clearly visible, detailing the model number, voltage, amperage, and specific wiring instructions for both line voltage and Class 2 low voltage ühendused.

4. Operatsioon

The MP20 Power Pack operates in conjunction with an external occupancy sensor. Once properly wired and powered, the power pack will respond to signals from the connected sensor. When the occupancy sensor detects presence, it will signal the MP20 to close its internal relay contacts, thereby supplying power to the connected load (e.g., lights). When the sensor no longer detects presence and its programmed delay expires, it will signal the MP20 to open its relay contacts, turning off the load.

The power pack provides the necessary low-voltage power (15 VDC) to the connected occupancy sensor, eliminating the need for a separate power supply for the sensor.

5. Hooldus

The SENSOR SWITCH MP20 Power Pack is designed for maintenance-free operation. However, periodic inspection is recommended to ensure optimal performance:

6. Veaotsing

If the MP20 Power Pack is not functioning as expected, consider the following troubleshooting steps:

If issues persist after performing these checks, contact customer support or a qualified electrician.

7. Tehnilised andmed

AtribuutVäärtus
Mudeli numberMP 20
Sisend Voltage120 / 277 VAC
Maksimaalne vool20 Amps
Väljund Voltage (Class 2)15 VDC
Mõõdud (P x L x K)3 x 1.8 x 3 tolli
Kaal9.6 untsi
HinnangUL 2043 Plenum Rated, UL Listed 3D62, cCSAus File #229654
KasutuskeskkondAinult siseruumides kasutamiseks
TootjaANDURILÜLITI

8. Garantii ja tugi

For specific warranty information regarding the MP20 Power Pack, please refer to the documentation provided with your purchase or contact SENSOR SWITCH directly. Warranty terms and conditions may vary.

For technical support, product inquiries, or further assistance, please contact SENSOR SWITCH:

Seotud dokumendid - MP 20

Preview SensorSwitch PP20 & SP20 Power Pack Datasheet | Acuity Brands
Tehnilised andmed ja rohkemview for the SensorSwitch PP20 and SP20 Power Packs, designed for low voltage sensor systems and lighting load switching. Includes features, warranty, ordering information, and electrical/mechanical specifications.
Preview SensorSwitch PP5 SSA toite-/releepakett: omadused, spetsifikatsioonid ja juhtmestik
SensorSwitch PP5 SSA toite-/releepaketi põhjalik juhend, mis kirjeldab üksikasjalikult selle omadusi, elektrilisi ja mehaanilisi näitajaid, keskkonnakaalutlusi, garantiid ja valgustusjuhtimissüsteemide juhtmestiku juhiseid.
Preview Acuity Controls MP20/MSP20 Power Relay Pack - Technical Specifications and Wiring
Detailed technical specifications, features, and wiring diagrams for the Acuity Controls MP20 Power Pack and MSP20 Secondary Relay Pack, designed for low voltage occupancy sensor lighting control systems.
Preview Metcalfe MP20 20-liitrine tugevatoimeline lauale paigaldatav mikser: paigaldus- ja kasutusjuhend
Metcalfe MP20 20-liitrise tugevatoimelise lauale kinnitatava mikseri põhjalik paigaldus-, kasutus-, puhastus-, hooldus- ja tõrkeotsingu juhend. Sisaldab tehnilisi andmeid, segamisvõimsust ja garantiiteavet.
Preview BOTEX UP-2RF moodulpaki RF kasutusjuhend - valgustuse juhtimine
Põhjalik kasutusjuhend BOTEX UP-2RF moodulpaketi RF kohta, mis kirjeldab funktsioone, töörežiime (DMX aadress, lülitipakett, dimmerpakett) ja professionaalse valgustuse juhtimise tehnilisi andmeid.
Preview KSTAR BluE-H5/H3 Energy Storage System: Installation, Operation & Maintenance Manual
Comprehensive manual for KSTAR BluE-H5/H3 Energy Storage Systems, including models like BluE-S 5000D and BluE-S 3680D. Covers installation, operation, maintenance, safety, and troubleshooting for DC-coupled, AC-coupled, and hybrid systems.